Home / Methods / Construction / Heat loss through a wall, window or roof
Heat loss through a wall, window or roof
How much heat goes through a wall, window or roof and how much insulation would save.
Or ask in your own words (needs an AI key)
What you need
- area, m²
- thermal transmittance U, W/(m²·K)
- layer thickness, mm (if U is unknown)
- thermal conductivity, W/(m·K)
- inside temperature, °C (default 20)
- average outside temperature for the period, °C
- hours in the period (heating season ≈ 4,000) (default 1)
- price per kWh of heat
What it calculates
- heat loss, W
- heat over the period, kWh
- cost of the lost heat
- U-value used, W/(m²·K)
Examples
100 m², U = 0.3, 20 °C vs −2 °C, 4,000 h, 4.32 per kWh
| heat loss | 660 W |
| heat over the period | 2,640 kWh |
| cost of the lost heat | 11,404.8 |
An 80 m² wall of 100 mm mineral wool (λ = 0.04), 20 °C vs −3 °C, 4,000 h, 2.5 per kWh
| heat loss | 689.139 W |
| heat over the period | 2,756.55 kWh |
| cost of the lost heat | 6,891.39 |
| U-value used | 0.3745 W/(m²·K) |
Example numbers are checked against an independent calculation. The AI in Numo does not compute: it only parses your question; a deterministic engine does the maths.
Careful
Transmission only; infiltration and ventilation often add as much. For a layer without U, surface resistances of 0.17 m²·K/W are added.
Typical mistakes
- Confusing U (lower is better) with resistance R = 1/U (higher is better).
- Using the design temperature of the coldest five days for seasonal energy: it sizes the boiler, while seasonal kWh need the average temperature.