Home / Methods / Engineering / Availability (SLA): what it means in downtime and what redundancy gives
Availability (SLA): what it means in downtime and what redundancy gives
What the "nines" mean in hours of downtime, how availability falls in a system of many dependent parts, and what duplication buys.
Or ask in your own words (needs an AI key)
What you need
- availability of one component, % (99.9 …)
- components in series (if one fails, everything stops) (default 1)
- parallel copies of each component (redundancy) (default 1)
What it calculates
- system availability, %
- downtime per year, h
- downtime per month, min
- downtime per day, s
- downtime per year of a single component with no redundancy, h
Examples
One component at 99.9%
| system availability | 99.9 % |
| downtime per year | 8.766 h |
| downtime per month | 43.83 min |
| downtime per day | 86.4 s |
Five components at 99.9% in series, each duplicated
| system availability | 99.9995 % |
| downtime per year | 0.0438 h |
| downtime per month | 0.2192 min |
| downtime per day | 0.432 s |
| downtime per year of a single component with no redundancy | 8.766 h |
Example numbers are checked against an independent calculation. The AI in Numo does not compute: it only parses your question; a deterministic engine does the maths.
Careful
Failures are assumed independent: a common cause (one power feed, one data centre) removes the gain from copies. A year is 365.25 days; the calculation does not distinguish short outages from long ones.
Typical mistakes
- Not multiplying availabilities: ten components at 99.9% in a chain give 99.0%, not 99.9.
- Placing copies with a shared cause of failure and treating them as independent.
Professions that use it
Infrastructure Engineer, Reliability Engineer
More in this family «Engineering»
- Simply supported beam: moment, stress, deflection
- Pipe pressure drop (Darcy–Weisbach)
- Reliability: probability of failure-free operation from MTBF and availability
- Stress and safety factor of a part
- Cable size by voltage drop
- Design load: permanent and variable actions with partial factors
- Column buckling (Euler)