Cable size by voltage drop
What cable to run to a garage, pump, boiler or machine so the voltage at the end does not sag.
Or ask in your own words (needs an AI key)
What you need
- current, A
- one-way line length, m
- voltage, V (230 single-phase, 400 three-phase) (default 230)
- allowed voltage drop, % (default 3)
- 1 — copper, 0 — aluminium (default 1)
- 1 — three-phase, 0 — single-phase (default 0)
What it calculates
- minimum cross-section by voltage drop, mm²
- nearest standard size, mm²
- voltage drop at the standard size, %
- power lost in the cable, W
Examples
16 A, 30 m, 230 V, 3%, copper
| minimum cross-section by voltage drop | 2.4348 mm² |
| nearest standard size | 2.5 mm² |
| voltage drop at the standard size | 2.9217 % |
63 A, 200 m, 400 V, 2%, aluminium, three-phase
| minimum cross-section by voltage drop | 76.3834 mm² |
| nearest standard size | 95 mm² |
| voltage drop at the standard size | 1.6081 % |
| power lost in the cable | 701.886 W |
Example numbers are checked against an independent calculation. The AI in Numo does not compute: it only parses your question; a deterministic engine does the maths.
Careful
Voltage drop only. The size must also pass the heating (ampacity) check for the installation method and match the breaker. Final word — an electrician.
Typical mistakes
- Using the one-way length without the factor: current flows there and back.
- Choosing the size by voltage drop alone, forgetting heating.
More in this family «Engineering»
- Simply supported beam: moment, stress, deflection
- Pipe pressure drop (Darcy–Weisbach)
- Availability (SLA): what it means in downtime and what redundancy gives
- Reliability: probability of failure-free operation from MTBF and availability
- Stress and safety factor of a part
- Design load: permanent and variable actions with partial factors
- Column buckling (Euler)