Cable size by voltage drop

What cable to run to a garage, pump, boiler or machine so the voltage at the end does not sag.

Calculate in Numo

Or ask in your own words (needs an AI key)

What you need

What it calculates

Examples

16 A, 30 m, 230 V, 3%, copper

minimum cross-section by voltage drop2.4348 mm²
nearest standard size2.5 mm²
voltage drop at the standard size2.9217 %

Calculate this example →

63 A, 200 m, 400 V, 2%, aluminium, three-phase

minimum cross-section by voltage drop76.3834 mm²
nearest standard size95 mm²
voltage drop at the standard size1.6081 %
power lost in the cable701.886 W

Calculate this example →

Example numbers are checked against an independent calculation. The AI in Numo does not compute: it only parses your question; a deterministic engine does the maths.

Careful

Voltage drop only. The size must also pass the heating (ampacity) check for the installation method and match the breaker. Final word — an electrician.